Double-motor Three-station Mechanism CJ8-6

The CJ8-6 operating mechanism can be used to close and open ZF23-126, ZF□-126, as well as disconnectors, earthing switches and load switches with torque requirements comparable to those of the above mentioned switches. The mechanism has three stations. One mechanism can operate one disconnecting switch and one earthing switch for closing and breaking of the disconnecting switch and closing and breaking of the earthing switch. The mechanism has both manual and electric modes of operation.

  Contact Now
Product Details

Product description

The CJ8-6 operating mechanism can be used to close and open ZF23-126, ZF□-126, as well as disconnectors, earth switches and load switches, with torque requirements comparable to those of the above mentioned switches.

The mechanism has three stations. One mechanism can operate one disconnecting switch and one earthing switch for closing and breaking of the disconnecting switch as well as closing and breaking of the earthing switch. The mechanism has both manual and electric operation modes.

Operating conditions

1. Ambient air temperature: upper limit +60℃, lower limit -30.

2. altitude: not more than 3,000 meters.

3. Barometric pressure: not more than 700Pa (equivalent to 34m/s air velocity).

4. No fire hazards, explosion hazards, heavy pollution, corrosive gases and severe vibration of the occasion.

Main technical parameters

1. The output angle of this mechanism can be customized according to user requirements.

2. The output torque after M is 120 136N.

3. Rated voltage, switching time is less than 2S.

4. Storage motor technical parameters.

Model

HDZ-23610C

Rated working voltage

~220V

Rated output power of motor

360W

Normal working voltage range

85%--110%

5. CSK Magnetic Burst Switches

One opening and one closing (or two opening and two closing), rated breaking current is 10A under AC220V, rated breaking current is 3A under DC220V.

6. Relay Type (can be provided or not according to user requirements)

Relay type: 3TH42-44; manufacturer Siemens; supply voltage DC220V (AC220V), DC110V (AC110V).

7. Wiring Terminals

The current that can be passed continuously is 10A.

8. F10 Auxiliary Switch

The rated breaking current of the contacts is 10A at AC220V and 5A at DC220V.

9. Auxiliary Socket

24-pin, 32-pin and 64-pin secondary sockets are available.

Mechanism Structure Schematic


Mechanism Structure Schematic


The structure has an overall flat appearance. The height of the mechanism is less than 150 mm, which is ideal for the requirements of a shared GIS mechanism. The on/off operation of the mechanism and the on/off indication are displayed on a flat surface. On the mounting surface of the mechanism there is a hole in the output shaft so that the output shaft of the switch in the mechanism can be connected to the output shaft of the mechanism and the drive train of the switch is not exposed, which facilitates sealing and gives the switch an aesthetic appearance. The secondary wiring of the mechanism is output from an industrial connector, which is of plug-in type to facilitate the electrical connection between the mechanism and the switch.

Ordering instructions

For other special requirements, please consult with the manufacturer for production.


Leave your messages